top of page

SLC-10-CUBE3+ B1

Buy Now

Email: sale@theupsteam.co.uk
Web Form

Enquire About The

Email: sale@theupsteam.co.uk
Web Form

SLC-10-CUBE3+ B1

UPS

Description

Salicru's SLC CUBE3+ series is a UPS range featuring high-performance, On-line double conversion (VFI) technology that provides a reliable, high-quality power supply and, at the same time, achieves significant energy and financial savings in terms of installation and operating costs.

Particularly noteworthy is the unit's input power factor (PF=1) and its extremely low distortion rate (THDi even lower than 1.5%), which help to reduce installation and operating costs, and contribute to improving the quality of the electrical grid.

The output power factor (PF=0.9) also stands out, providing optimum electrical protection for computer systems and low harmonic output distortion (THDv even lower than 0.5%), enabling it to protect any type of load (inductive, resistive, capacitive or mixed). In addition, the performance achieved (up to 95% in On-line mode and 98.4% in Smart Eco-mode) produces significant energy consumption savings and reduces air conditioning needs.

For a full optimum solution, the SLC CUBE3+ provides maximum adaptability (even with the standard model), the possibility of parallel redundant expansion and extensive communication options. Finally, also worth noting is the unit's lightweight design and reduced dimensions, enabling it to be easily installed and ensuring that footprint is minimal.

Technical Specifications

TECHNOLOGY - On-line, double conversion, HF, DSP control


INPUT

Voltage - 220 / 230 / 240 V - 3 x 380 / 3 x 400 / 3 x 415 V (3F + N)

Voltage range - +15% / -20% (configurable)

Rated frequency - 50 / 60 Hz

Total harmonic distortion (THDi) - 100% load: <1.5% / 50% load: <2.5% / 10% load: <6.0% 

Power factor - 1 from 10% load

Rectifier topology - Three-phase IGBT full wave, soft start, PFC, transformerless


OUTPUT

Power factor - 0.9

Voltage - 220 / 230 / 240 V - 3 x 380 / 3 x 400 / 3 x 415 V (3F + N)

Dynamic accuracy - ± 2% dynamic

Static accuracy - ± 1% steady

Response time accuracy - 20 ms para saltos de carga 0%÷100% y caída de tensión hasta -5%

Power (VA/W) - 10000 / 9000

Total harmonic distortion (THDv) Linerar load - <0.5%

Total harmonic distortion (THDv) Non~linear load - <1.5% (EN-62040-3)

Synchronised frequency - 50/60 Hz ±5 Hz (selectable)

Frequency accuracy (battery mode) - 50/60 Hz ±0.05%

Synchronous speed - From 1 Hz/s to 10 Hz/s (programmable)

Eco-mode performance - 95%

Total performance in On-line mode - 7.5÷60 kVA: 92.0%÷93.0% / 80÷200 kVA: 94.0%÷95.0%

Admissible overloads - 125% for 10 min / 150% for 60 s / >150% for 20ms

Crest factor - 3,4 a 1


MANUAL BYPASS

Type - No breaks


STATIC BYPASS

Type and activation criteria - Solid state, controlled by microprocessor

Transfer times in Smart Eco-mode (ms) - 4 ms (typical)

Transfer times in On-line - Nil

Transfer to bypass - Immediate, for overloads exceeding 150%

Retransfer - Automatic, after alarm deactivation


BATTERY

Battery type - Lead acid, sealed, maintenance free

Charging voltage regulation - Batt-Watch


COMMUNICATION

Ports - 1 x RS232/RS485 + 1xUSB,with Modbus protocol

Relay interface - 4 x AC failure, bypass, low battery and general

Intelligent slot - 1, for SNMP

Monitoring software - Viewpower / UPSMAN

Backlit LCD display - LCD display, LEDs and keyboard


GENERAL

Operating temperature - 0º C ÷ +40º C

Relative humidity - Up to 95%, non-condensing

Maxium operating altitude - 2,400 masl (3)

Acoustic noise at 1 metre - <52 dB(A)(2)


SYSTEMS

Maximum no. parallel systems - Yes, up to 4 units


STANDARDS

Safety - EN-IEC 62040-1

Electromagnetic compatibility (EMC) - EN-62040-2

Operation - VFI-SS-111 (EN-62040-3)

Quality and environmental management - ISO 9001 & ISO 14001


DIMENSIONS

Depth (mm) - 770

Width (mm) - 450

Height (mm) - 1100


WEIGHT

Weight (kg) - 100


(1) Up to 60 kVA.

(2) Only for three-phase input / output models. FP = 0.8 for other configurations..

(3) <65 dB(A) for 80 to 120 kVA models / <70 dB(A) for 160 to 200 kVA models

(4) Power derating for higher altitudes up to 5000 masl.

Related Products

bottom of page