Description
Salicru’s SLC X-PERT series consists of three-phase UPSs that combine very low total cost of ownership (TCO) with very high efficiency and compact design, providing high-quality uninterruptible power for all critical applications. The technology incorporated offers one of the highest efficiencies on the market in VFI mode and 100% of expected battery life.
The SLC X-PERT series maximises the use of the surface occupied thanks to its high power density design. Models from 200 kVA have complete front access, precluding the need for side or rear space, making them easy to maintain and installable side by side, back to back or against a wall. The common battery option further enhances the ability of the SLC X-PERT series to deliver low footprint solutions, freeing space for other equipment.
Technical Specifications
TECHNOLOGY - On-line, double-conversion, DSP control
INPUT
Voltage - 3 x 380 V / 3 x 400 V / 3 x 415 V (3F+N)
Voltage range - +15% / -20% (@ 3 x 400 V)
Rated frequency - 50 / 60 Hz (45-65 Hz)
Frequency range - ±10%
Total harmonic distortion (THDi) - <3%
Power factor - >0.99
OUTPUT
Power factor - 1
Voltage - 3 x 380 V / 3 x 400 V / 3 x 415 V (3F+N)
Total harmonic distortion (THDv) Non~linear load - <5%
Synchronised frequency - ±2 Hz
Frequency- 50 / 60 Hz
Frequency accuracy (battery mode) - ±0.001 Hz
Synchronous speed - <1Hz/s
High-efficiency performance - Up to 97%
Eco-mode performance - ≥98%
Total performance in On-line mode - ≥95.5%
Performance in Smart Eco-mode - &ge98%
Admissible overloads -125% for 10 min / 150% for 1 min
Crest factor - 3 a 1
STATIC BYPASS
Type and activation criteria - Solid state, microprocessor controlled
Voltage (V) - Three-phase 3 x 380 V / 3 x 400 V / 3 x 415 V (3P+N)
Transfer to bypass - Immediate, for overloads exceeding 150%
Retransfer - Automatic after alarm discontinuation
Frequency range - ±10% (selectable)
Voltage range - ±10% (selectable)
Input - Independent
Frequency - 50 / 60 Hz
Admissible overloads - 1000% for 1 cycle
BATTERY
Battery type - Lead acid, sealed, maintenance free(1)
Charge type - Type of charge IU (DIN 41773)
COMMUNICATION
Ports - RS-232, USB
Backlit LCD display - 10” touch screen
GENERAL
Operating temperature - 0 ÷ +40ºC
Storage temperature - -10ºC ÷ +40ºC (with battery) / -10ºC ÷ +70ºC (no battery)
Relative humidity - 95% non-condensing
Maxium operating altitude - 2400 m.a.s.l.(2)
Acoustic noise at 1 metre - "<60dB up to 160kVA; <65dB up to 300kVA; <72dB for 400kVA"
STANDARDS
Safety - EN-IEC 62040-1
Electromagnetic compatibility (EMC) - EN-62040-2
Operation - EN62040-3 (VFI-SS-111)
Quality and environmental management - ISO 9001 & ISO 14001
DIMENSIONS
Depth (mm) - 970
Width (mm) - 880
Height (mm) - 1975
WEIGHT
Weight (kg) - 850
(1) Ni-Cd, Li-Ion and other types of battery available on request.